Ground Resistance Testers 3-4 Pole

MAIN MENU

.......................................

......
Catalog:Ground Resistance Testers 3-4 Pole


Biddle Model DE2/2 High Sensitivity Ground/Earth RT Cat-250202

Description

Click here to view full-pdf specification sheets

MEGGER DET2/2

Accurately measures ground resistance under the most demanding conditions
High resolution - 0.001 W, with autoranging
Simple menu driven operation
The DET2/2 digital ground resistance tester provides a wide resistance range from 0.010 W to 19.99 kilohms for testing larger or more complex grounding systems and for difficult testing environments, with ±0.5% accuracy and 0.001 W resolution. Microprocessor control and advanced filtering simplify testing in environments with high levels of interference.

Applications

The DET2/2 Earth Tester is a reliable instrument designed for larger or more complex earthing systems, including communications earthing systems and difficult testing environments. It may be used to test in accordance with BS 7430 (1991), the IEE Wiring Regulations and VDE 0413 part 7 (1982). The instrument is suitable for soil resistivity measurements, which are used to establish the optimum electrode design and site, as well as perform archeological and geological investi-gations.
Resistivity tests assist in the design of a correct earth system and avoid the cost of re-working electrode installations.
Earth testing kits, which include suitable test spikes and test leads, are available separately.

Features

• High resolution – 1 m½ –
ideal for large earthing systems
• High accuracy for earth electrode and soil resistivity testing
• Test voltage 50 V max. for safety
• Rechargeable battery power with long battery life and rapid re-charge
• A robust, versatile instrument with IP54 protection
• Filter and high current features to enable valid earth testing in difficult situations

Specifications

Please see pdf. for more detailed specifications

Earth Resistance Range
0,010 ½ to 19,99 k½ (auto-ranging),
1 m½ resolution.

Accuracy (23 °C = 2 °C)
±0,5% of reading ± 2 digits

Service Error
±5% of reading ± 2 digits ± 10 m½
(meets VDE service error over 50 m½)

Comply with Standards
BS 7430 (1991)
VDE 0413 Part 7 (1982)

Test Frequency
105 to 160 Hz reversing d.c. (50 Hz
operation default to 128 Hz, 60 Hz
operation default to 150 Hz) Set in
steps of 0,5 Hz

Test Current
50 mA max (selectable high and low
levels)

Maximum Output Voltage
< 50 V r.m.s.

Ordering Details

Auto Earth Tester DET2/2

Included Accessories
Mains supply lead for battery charging
Operating instruction book

Optional Accessories


Click here to purchase accessories

Please call 1800 783 6664 for any items not listed

Model

Auto Earth Tester DET2/2

Please order from the menu below


Price : US$ 4,350.00