  DO 1000 Controller


DO 1000 Controller

Use for accurate dissolved oxygen control in your wastewater or aquaculture process

   Large dual LCD shows DO plus temperature simultaneously
   Two set point,two SPDT relay operation- choose from lo/lo hi/lo or hi/hi control
   Select between three control modes: on/off, proportional pulse length or proportional pulse frequency
   Separate alarm relay
   Push button one- or two-point calibration
   Key in salinity and pressure manually, the controller automatically calculates offset values
   Selectable readout in mg/l, ppm or % saturation
   Separately adjustable high and low set point hysteresis bands
   Transmitter/recorder output for hard copy recording
   Two level password protection
   LED indicators signal control activities
   Built-in memory backup

Our OAKTON 1000 series 1/4 DIN dissolved oxygen controller features independent 100% and zero adjustment calibrations and offset adjustment capabilities to ensure high accuracy for your exact conditions. Its 0 to 2000 second selectable time delay and adjustable set point hysteresis bands means you can tailor control relay action to your specifications.

Each unit is selectable for isolated 0-20 or 4-20 mA transmitter/recorder output; 110 or 220 VAC; normally open or closed relays; and manual or automatic temperature compensation. The compact 1/4 DIN size fits into standard panel cutouts. The IP54 rated front panel keypad is weather resistant. Includes mounting hardware.

Click below to download Acrobat (.pdf) file of:
DO 1000 controller product bulletin
DO 1000 controller manual
Tech Tip: Comparison between Polargraphic and Galvanic DO sensor technologies

 
Measures Dissolved oxygen, °C
% saturationRange 0.00 to 200%
% saturationResolution 1%
% saturationAccuracy ±1.5% full-scale
mg/l (ppm)Range 0.0 to 20.00 mg/l (ppm)
mg/l (ppm)Resolution 0.01 mg/l (ppm)
mg/l (ppm)Accuracy ±1.5% full-scale
TemperatureRange 0 to 50°C
TemperatureResolution 0.1°C
TemperatureAccuracy ±0.5°C
CalibrationDissolved oxygen one or two points (100% and 0% saturation)
CalibrationTemperature offset up to ±5°C
Control type on/off or proportional (selectable)
Number of inputs one
Number of set points two (high and low)
Separate alarm relay yes
OutputControl 2 SPDT relays, 6 A at 110 VAC, 250 VAC maximum
OutputAlarm 1 SPDT relay, 6 A at 110 VAC, 250 VAC maximum
OutputPulse pulse length (0.5 to 20 sec) or pulse frequency (60 to 120 pulses per min)
OutputCurrent isolated 0-20.4-20 mA, with 20% to 100% full-scale scalable boundaries, 600 maximum load
Hysteresis 0.1 to 1.0 mg/l; 1 to 10%
Relay delay selectable, 0 to 2000 seconds
Input impedance 10^12 M
Electrical isolation yes, galvanically
Salinity correction manual input from 0.0 to 50.0 ppt; automatic correction
Barometric pressure correction manual input from 0.0 to 50.0 ppt; automatic correction
Temperature Sensor 100 Pt RTD
Temperature Compensation Automatic or manual from -9.9 to 125°C
Password protection two level password
Display dual line LCD, 4-digit upper and 3 1/2 digit lower
Operating Temperature -10 to 60°C
Housing 1/4 DIN
Dimensions 3.8" x 3.8" x 6.9" (9.6 x 9.6 x 17.5 cm)
Shipping weight 2.5 lbs (1.2 kg)

 

 
Model # Description
WD-35201-00 DO 1000 controller, 110 VAC
WD-35201-05 DO 1000 controller, 220 VAC
WD-35201-52 Industrial DO probe, 0 to 10 ppm
WD-35201-50 Industrial DO probe, 0 to 40 ppm