CATEGORY

Current / Voltage Loggers / Power

MAIN MENU

.......................................

......
Catalog:Current / Voltage Loggers / Power


AEMC PQL 100 Power Meters & Loggers


Features

The PQL 100 Series is a single phase Power Quality Logger designed to measure and log from a complete suite of electrical and power quality parameters. It is accompanied by an easy-to-use report compliant software package.

Portable, compact unit - plugs into standard US 120V outlets
Simple operation: Plug in, Record, Download & Read
Measures and stores electrical parameters: V, A, Hz & more

Measures and stores power parameters: W, VA, Var, Demand, Peak Demand & more
Measures and stores power quality parameters: Harmonics, THD (rms & fundamental), K-factor & more
Automatically captures worstcase Surge, Sag & THD waveforms
High accuracy & resolution: 128 samples/cycle, 16 bit resolution
LEDs indicate mode of operation
Records up to 12 data channels
Powered from voltage input channel
Battery backup data integrity during power outages and programmed configuration for up to 1 year
Optically isolated RS-232 output for direct connection to a PC
IEC 1010, 150V, Cat. III
Includes DataView Lite Analysis & Reporting Software


Applications:

Monitor power quality in North American commercial, industrial and residential application
Monitor power quality at computer workstations
Monitor power quality on laboratory equipment


Specifications

Electrical Specifications
Voltage
Range 0 to 140V
Resolution 0.1V
Accuracy ±(0.3% of Reading + 0.3V)

Current
Range 0 to 15A (70A peak maximum)
Resolution 0.01A
Accuracy ±(0.5% of Reading + 0.03A) @ 0.75A to 15A; ±0.30A @ < 0.75A

Frequency
Range 45 to 65Hz
Resolution 0.01Hz
Accuracy 0.1Hz

Programmable Parameters

RMS, Min. & Max of the following parameters:

Voltage, Current, Frequency, Even Voltage
Real Power (W), Reactive Power (Var) and Apparent Power (VA)
Total Harmonic Distortion for Voltage and Current (IEEE or IEC Definition)(See Automatic Storage)
Power Factor (Total and Displacement)
K-Factor

Demand 10/15/30 minutes or user-definable
Peak Demand Over demand period
Voltage Sag User-definable magnitude (See Automatic Storage)
Voltage Surge User-definable magnitude (See Automatic Storage)

Input
Input Channels 1 Voltage / 1 Current
Sample Rate 128 per cycle per channel

Recording
Storage Rate 125ms to 7 days
Recording Session Length 15 minutes to 8 weeks selectable from table or user programmable
Total Memory 128KB (64,000 records maximum)
Date and Time MM/DD/YY hh/mm/ss.sss

Automatic Storage

Five worst-case THD waveforms for each for Voltage and Current: One per 1/5 of recording session length

Five worst surge (duration X magnitude) & sag occurrences are automatically recorded in high-resolution mode (RMS value of each cycle is recorded for 128 cycles at the entry and 128 cycles at the exit of the surge/sag) regardless of the storage rate selected. One waveform per each occurrence of the worst-case surge/sag with the worst THD is stored. A table for the 100 worst-case occurrences of the surge/sag is maintained. The table stores time & date, duration & magnitude of each surge/sag including the high-resolution mode surge/sag. In addition, an Event Counter is maintained for all occurrences of the surge/sag.

Operation
Indicators
Red: Solid on when AC voltage is present
Yellow: Solid on when data stored in memory. Single blinks when memory is full
Green: Single blinks when the logger is in Standby mode. Double blinks when the logger is in Recording mode

Controls
Record Start/Stop
Reset

Power Supply
Power Supply 75V to 140V @ 45Hz to 65Hz

Battery
Internal NiCD rechargeable battery-pack which continuously charges from the power line. Provide 30 minutes of ride-through in case of power loss during recording and provides 1 year of memory backup when fully charged
Internal Li battery for additional memory backup up to 1 month

Unit is powered from the power line in normal operation.

Serial Interface
Output RS-232 via DB9 connector
Isolation Optically isolated. 2500V maximum
Baud Rate 9600, 19.2K. Selectable from DataView

Mechanical Specifications
Material: UL94V-0 polycarbonate (ABS)
Dimensions: 5.91 x 3.15 x 2.36" (150 x 80 x 60mm)
Weight: 1lb 7oz (650g) including the batteries

Environmental Specification
Operating Temperature: 14° to 122°F (-10° to 50°C)
Storage Temperature: -4° to 140°F (-20° to 60°C)
Relative Humidity: 0% to 85% @95°F (35°C), non-condensing

Safety / Reference Specifications
Safety: IEC 1010-1, 150V, Pollution Degree 2, Cat. III


Accessories

Please call 1800 783 6664