AEMC L215 AC Voltage Logger


Features

The AC Exception Voltage Simple Logger Model L215 is the ideal product to capture short-term events such as sags and swells. This logger samples the input 10 times per second and only stores the data when an alarm threshold is crossed, thus maximizing its use of memory. The 65,000-point storage capacity provides enough memory to store more than 1000 events. The Model L215 is powered by the AC voltage signal it is monitoring and incorporates a backup battery to provide up to one year of additional operation and data storage protection.

0 to 250Vrms
10 samples per second
Stores data when alarm level is tripped
True RMS measurements
64K storage memory
10 bit resolution (250mV)
Detect sags and swells
Scale automatically selected by software
Software programmable HI and LO alarm levels
Alarm trip LED indicator


Applications:

Surge/sag monitoring
Computer room monitoring
Residential monitoring
Machine monitoring
Marine power monitoring

Specifications

Electrical Specifications

Number Of Channels: 1
Measurement Range: 0 to 250Vrms
Input Connections: Recessed safety banana jacks
Resolution: 10 bit, 250mV max
Accuracy: 1% of Reading +250mV
Sample Rate: 36,000/hr (10 samples/sec)
Data Storage: Approximately 65, 536 readings
Data Storage Technique: Exception recording in FIFO mode; 60 samples stored when alarm is tripped. Each 60 sample recording is considered to be a packet. When memory is full, data will be overwritten one packet at a time beginning with the oldest.
Power Source: AC powered with 9V Alkaline battery backup
Battery Life: Up to 1 yr of recording @ 25° C
Output: RS-232 via DB9 connector (@4800 baud)
Indicators: Red LED double flashes in LOGGING, single flashes in STANDBY and is off in OFF mode. Amber LED flashes once every 2 seconds when alarm level has been tripped. Amber light can only be reset by stopping the recording and downloading the data.
Controls: One button used to start and stop recording sessions and to turn the data logger on and off

Mechanical Specifications

Size: 2-7/8 x 2-5/16 x 1-5/8" (73 x 59 x 41 mm)
Weight: 5 oz (140g)
Mounting: Base plate mounting holes or Velcro pads supplied loose
Case Material: Polystyrene UL VO

Environmental Specification

Operating Temperature: -4 to +158° F (-20 to +70° C)
Storage Temperature: -40 to +174° F (-40 to + 80° C)
Relative Humidity: 5 to 95% non-condensing
Protection Index: NEMA2
Software Compatibilty: Windows 3.1, Windows 95, Windows 98

Safety / Reference Specifications